The output of my PID controller is coming very high...
10 views (last 30 days)
Show older comments
The output of my PID controller is coming as high as -10e15. What could be the possible reason and how to limit it????
Thanking you in advance...
1 Comment
baosen zhao
on 15 Apr 2024
我的想法是在实际的热工对象控制中,如果有很高的PID控制器输出,直接就切断PID的控制,此时相当于给系统一个负阶越响应,PID的控制器降至合理的区间就会继续打开PID的控制
Answers (2)
Christoph F.
on 26 Sep 2017
Edited: Christoph F.
on 26 Sep 2017
Without more information, perhaps the simulink diagram, the question will be difficult to answer.
In general, PID controllers will produce high outputs if:
1) P coefficient > 0 and the input value is high
2) D coefficient > 0 and the input signal has steep slopes
3) I coefficient > 0 and the average control error does not approach zero over time; i.e. the integrator just keeps integrating up the error.
3) can be remedied by anti-integrator-windup measures (there are several approaches with different complexities and side effects. I believe the Simulink PID controller block does offer this as a built-in feature.
0 Comments
See Also
Community Treasure Hunt
Find the treasures in MATLAB Central and discover how the community can help you!
Start Hunting!